// products · L2 field instrument

IR·SF₆
Room and leak monitoring for SF₆ and refrigerants.

Stationary NDIR transmitter for SF₆ and F-gas refrigerants in GIS halls, substations and machine rooms. Dual-beam optics with reference channel and heated cell — stable zero for years, IP65, Modbus RTU.

0–1000 / 0–2000 ppm SF₆
t₉₀ ≤ 15 s
IP65 · −40…+60 °C
RS-485 Modbus RTU
ShareLinkedInEmailWhatsAppX
L2 · field instrumentIR·SF₆
Tremon IR·SF₆
Specifications

Typical values from the datasheet; accuracy applies under the datasheet's reference conditions. Where a value depends on the application it is specified per project and fixed in the order confirmation.

gasSF₆ + refrigerants (F-gas)
range0–1000 / 0–2000 ppm (0–6000 / 0–12000 mg/m³)
optics2-beam + reference · heated cell
responsewarm-up 60 s · t₉₀ ≤15 s
interfaceRS-485 Modbus RTU
buildIP65 · −40…+60 °C · aluminium
Downloads

Open links — no form.

DocumentFileType
Datasheettremon-ir-datasheet.pdfPDF · 5 MB
Manualtremon-ir-sf6-manual.pdfPDF · 13 MB
Calibration certificate (sample)on request — issued per unitPDF
Modbus register mapon requestPDF
Applications and the rule behind each
  • GIS halls and cable basements: SF₆ at floor level (heavier than air)
  • Refrigeration machine rooms per EN 378 (R-134a, R-125 blends, R-22 legacy)
  • Fire-suppression rooms (R-227ea) leak detection
  • Multi-point sampling with GDC-S52
Gases

Each gas has a reference page with limits, IR band and monitoring practice.

Certificates and compliance

Status words as on the datasheet: certified · pending · application dependent.

IP65certified
CEcertified
ISO 17025-method calibrationper unit
How you get it
1
gas · range · mounting
2
quote & delivery
3
wall mount 15 cm above floor · RS-485 to GDC / SCADA
4
annual zero/span check with magnetic wand
FAQ
Where to mount?
15 cm above floor level in GIS halls and cable basements — SF₆ is five times heavier than air and pools low.
How is it calibrated in the field?
Zero/span check with a test gas and a magnetic wand; the calibration record per unit is traceable to national standards.
Does it detect refrigerants?
Yes — F-gas refrigerants (R-134a, R-125, R-22, R-227ea) with the corresponding range configuration.
Get a quote

Tell us what you measure — just tap

Three taps and an email. An engineer replies within 24 h with feasibility and a price indication.